Sensepoint XCD Detector | ||||||||||||||
Use | 3 wire, 4-20mA and RS485 MODBUS output fixed point detector with in-built alarm and fault relays for the protection of personnel and plant from flammable, toxic and Oxygen hazards. Incorporating a transmitter with local display and fully configurable via non-intrusive magnetic switch interface. Wide range of sensors available. | |||||||||||||
Electrical | ||||||||||||||
Input Voltage Range 16 to 32VDC (24VDC nominal) for ATEX/IECEx/AP Versions 12 to 32VDC (24VDC nominal) for UL/CSA version
Max Power Consumption Maximum power consumption is dependent on the type of gas sensor being used. Electrochemical cells = 3.7W, IR = 3.7W and catalytic = 4.9W. Maximum inrush current = 800mA at 24VDC Current Output Sink or source ³0.0<1.0mA Fault 2.0mA or 4.0mA (17.4mA) Inhibit (during configuration/user settings) 4.0mA to 20.0mA Normal gas measurement 22.0mA Maximum over range Terminals 15 x screw terminals suitable for wire diameter 0.5mm2 to 2.5mm2 (20AWG to 13AWG) Relays 3 x 5A@250VAC. Selectable normally open or normally closed (switch) and energised/de-energised (programmable) Alarm relays default normally open/de-energised. Fault relay default normally open/energised Communication RS485, MODBUS RTU (Optional) |
||||||||||||||
Construction | ||||||||||||||
Material
Weight (approx) Mounting |
Housing Epoxy painted aluminium alloy LM25 or 316 stainless steel
Sensor 316 stainless steel Weather Protection Plastic Aluminium Alloy LM25 2.0kg (4.4lbs) 316 Stainless Steel 5.0kg (11lbs) Integral mounting plate with 4 x mounting holes suitable for M8 bolts Optional pipe mounting kit for horizontal or vertical pipe Ø1.5 to 3″ (2″ nominal) |
|||||||||||||
Entries | European ATEX/IECEx versions: 2 x M20 cable entries
North American UL/c-UL versions: 2 x ¾”NPT conduit entries. Suitable blanking plug supplied for use if only 1 entry used. Seal to maintain IP rating |
|||||||||||||
Detectable Gases and XCD Sensor Performance | ||||||||||||||
Gas | User Selectable Full Scale Range | Default Range | Steps | User Selectable Cal Gas Range | Default Cal Point | Response Time (T90) Secs | Accuracy | Operating Temperature*
Min Max |
Default Alarm Points
A1 A2 |
|||||
Electrochemical Sensors | ||||||||||||||
Oxygen | 25.0%Vol. only | 25.0%Vol. | n/a | 20.9%Vol. (Fixed) | 20.9%Vol. | <30 | <+/-0.5%Vol. | -20°C / -4°F | 55°C / 131°F | 19.5%Vol. ▼ | 23.5%Vol. ▲ | |||
Hydrogen Sulphide | 10.0 to 100.0ppm | 50.0ppm | 1ppm |
30 to 70% of selected full scale range |
25ppm | <50 | <+/-1ppm | -20°C / -4°F | 55°C / 131°F | 10ppm ▲ | 20ppm ▲ | |||
Carbon Monoxide | 100 to 1,000ppm | 300ppm | 100ppm | 100ppm | <30 | <+/-6ppm | -20°C / -4°F | 55°C / 131°F | 100ppm ▲ | 200ppm ▲ | ||||
Hydrogen | 1,000ppm only | 1,000ppm | n/a | 500ppm | <65 | <+/-25ppm | -20°C / -4°F | 55°C / 131°F | 200ppm ▲ | 400ppm ▲ | ||||
Nitrogen Dioxide | 10.0 to 50.0ppm | 10.0ppm | 5.0ppm | 5.0ppm | <40 | <+/-3ppm or +/-20% | -20°C / -4°F | 55°C / 131°F | 0.7ppm ▲ | 2.0ppm ▲ | ||||
Catalytic Bead Sensors | 25 to 95% of selected full scale range | |||||||||||||
Flammable 1 to 8* | 20 to 100%LEL | 100%LEL | 10%LEL | 50%LEL | <25 | <+/-1.5%LEL | -20°C / -4°F | 55°C / 131°F | 20%LEL ▲ | 40%LEL ▲ | ||||
Infrared Sensors |
30 to 70% of selected full scale range |
|||||||||||||
Methane | 20 to 100%LEL | 100%LEL | 10%LEL | 50%LEL | <30 | <+/-1.5%LEL | -20°C / -4°F | 55°C / 131°F | 20%LEL ▲ | 40%LEL ▲ | ||||
Propane | 20 to 100%LEL | 100%LEL | 10%LEL | 50%LEL | <30 | <+/-1.5%LEL | -20°C / -4°F | 55°C / 131°F | 20%LEL ▲ | 40%LEL ▲ | ||||
Carbon Dioxide | 2.00%Vol. | 2.00%Vol. | n/a | 1.00%Vol. | <30 | <+/-0.04%Vol. | -20°C / -4°F | 55°C / 131°F | 0.40%Vol. ▲ | 0.80%Vol. ▲ | ||||
NOTES ▲ – Rising Alarm ▼ – Falling Alarm
Performance data is: 1. Taken at nominal 20°C, 50%RH. 2. Applicable over the range 10 to 90% full scale. 3. Measured on units calibrated at 50% full scale. 4. Accuracy at 10% of default full scale (typical A1 alarm) of applied gas, or minimum (whichever is greater). 5. Measured at 500ml/min for IR, Toxics and O2, 1 Ltr/min for Catalytic bead using the calibration cup (S3KCAL). *Extended operating temperature range of -40°C to +65°C (-40°F to +149°F) for all sensors except for IR and H2 EC sensors, with an accuracy of +/- 30% of applied gas from -20°C to -40°C (-4°F to -40°F) and +55°C to +65°C (+131°F to +149°F). Long term operation at this range may cause decline in sensor performance. Contact Honeywell Analytics for any additional data or details. |
||||||||||||||
Certification | ||||||||||||||
European International China
Korea North America |
ATEX II 2 GD Ex d IIC Gb T6 (Ta -40ºC to +65ºC) T5 (Ta -40ºC to +75ºC) Ex tb IIIC T85°C Db IP66 T100ºC (Ta -40ºC to +75ºC) IECEx Ex d IIC Gb T6 (Ta -40ºC to +65ºC) T5 (Ta -40ºC to +75ºC) Ex tb IIIC T85°C Db IP66 T100ºC (Ta -40ºC to +75ºC)
GB Ex d IIC T4 GB3836.1&2 -2000, PA, CCCF KTL Ex d IIC T6 (-40°C to +65°C) UL/c-UL – Class I, Division 1, Groups B, C and D, Class I, Division 2, Groups B, C & D, Class II, Division 1, Groups E, F & G, Class II, Division 2, Groups F & G. -40ºC to +65ºC |
|||||||||||||
EMC | EN50270:2006 EN6100-6-4:2007 | |||||||||||||
Performance | ATEX, EN60079-29-1:2007 (flammable), EN45544 (Toxic), EN50104 (Oxygen), EN50271
China: PA Pattern Measurement (for transmitter and toxic gas sensors) “CCCF” Shenyang for Flammable (fire dept approval) CSA C22.2-152 |